IEC disc insulators specifications

IEC disc insulators include U40C, U40B, U70BL, U70C, U70BS, U70BL, U80BL, U80BS, U100BL, U100BL, U120B, U160BL , U160BS, U160BS, U160BL, and U160BL, as well as specifications.

IEC disc insulators drawings:

IEC disc insulators drawingIEC disc insulators drawingIEC disc insulators drawingIEC disc insulators drawing

IEC disc insulators drawingIEC disc insulators drawingIEC disc insulators drawing

IEC disc insulators drawingIEC disc insulators drawing


IEC disc insulators specifications:

Class
U40C
U40B
U70BL
U70C
U70BS
U70BL
Unit Spacing (H)-mm
140
110
146
146
127
146
Nominal Diameter (D)-mm
190
175
255
255
255
255
Coupling size
--
11
16A/B
16C
16A
16A/16B
Nominal Creepage Distance-mm
200
185
295
295
295
320
Rated E & M Failing Load-KN
40
40
70
70
70
70
Routine Tensile Load-KN
20
20
35
35
35
35
Impact Strength-N.m
5
5
6
6
6
6
Power Frequency Withstand
Wet-KV
30
30
40
40
40
40
Dry-KV
55
55
70
70
70
70
Dry Lighting Impulse Withstand Voltage-KV
75
75
110
110
110
110
Power Frequency Puncture Voltage-KV
90
90
110
110
110
110
Radio Interference Voltage
Test Voltage to Ground-KV
7.5
7.5
10
10
10
10
Max. RIV at 1MHz-uV
50
50
50
50
50
50
Weight-kg
2.5
2.4
4.8
4.7
4.7
5.0

 

Class
U80BL
U80BS
U100BL
U100BL
U120B
Unit Spacing (H) - mm
146
140
146
146
146
Nominal Diameter (D) -mm
255
255
255
280
255
Coupling size
16A/B
16A/B
16A/B
16A/B
16A/B
Nominal Creepage Distance-mm
295
295
295
340
320
Rated E & M Failing Load-KN
80
80
100
100
120
Routine Tensile Load-KN
40
40
50
50
60
Impact Strength-N.m
6
6
7
7
7
Power Frequency Withstand
Wet-KV
40
40
40
40
40
Dry-KV
70
70
70
70
70
Dry Lighting Impulse Withstand Voltage-KV
110
110
110
110
110
Power Frequency Puncture Voltage-KV
110
110
110
110
110
Radio  Interference Voltage
Test Voltage to Ground-KV
10
10
10
10
10
Max. RIV at 1MHz-uV
50
50
50
50
50
Weight-kg
5.4
5.2
5.7
6.2
5.8

 

Class
U160BL
U160BS
U160BS
U160BL
U160BL
Unit Spacing (H) -mm
255
255
280
300
255
Coupling size
20
20
20
20
20
Nominal Creepage Distance-mm
305
320
315
400
390
Rated E& M Failing Load-KN
160
160
160
160
160
Routine Tensile Load-KN
80
80
80
80
80
Impact Strength –N.m
10
10
10
10
10
Power Frequency Withstand
Wet-KV
40
40
45
45
40
Dry-KV
70
70
75
75
70
Dry Lighting Impulse Withstand Voltage-KV
110
110
110
110
110
Power Frequency Puncture Voltage – KV
110
110
110
110
110
Radio Interference Voltage
Test Voltage to Ground-KV
10
10
10
10
10
Max. RIV at 1MHz-uV
50
50
50
50
50
Weight -kg
7.0
7.2
7.6
8.3
7.6


Relative Articles:
disc insulators
Polymer disc insulator
33KV polymer disc insulator
ANSI Porcelain disc insulator

©2014 Zhengzhou Orient Powe Co., Ltd All rights reserved.  sales@orientinsulators.com
Orient Group is a professional manufacturer and exporter of composite suspension insulator and porcelain disc suspension insulator.