Porcelain Station Post Insulator

Porcelain Station Post Insulator widely used on transformer, distribution line, network and other electrical line. There are two general types for the insulators: normal type and anti-pollution type.

Porcelain Station Post Insulator details:
Solid-Core Station Post Insulators to meet ANSI C29.9 have the specific types as follows:
TR-202, TR-205, TR-208, TR-210, TR-214, TR-216, TR-286, TR-287, TR-288, TR-289, TR-291, TR-304, TR-312, TR-362, TR-369, TR391
Available color: grey, Brown

Porcelain Station Post Insulator

Porcelain Station Post Insulator drawings:

Porcelain Station Post Insulator drawings

Porcelain Station Post Insulator parameters:

Figure No.
TR-205
TR-208
TR-210
TR-214
TR-216
Figure No.
1
2
3
4
5
Creepage Distance mm
394
610
940
1092
1829
Cantilever Strength kN
8.9
8.9
8.9
8.9
6.7
Tensile Strength kN
38
44.5
53
62
71
Torsion Strength N.m
791
904
1130
1356
1695
Compression Strenth kN
44.5
44.5
66.7
66.7
111
Low Frequency Flashover Voltage KV
Dry Flashover
85
110
145
170
235
Wet Flashover
55
75
100
125
180
Critical Impulse Falshover Voltgae KV
Positive
125
170
225
280
390
Negative
200
250
290
340
475
Low Frequecy Withstand Voltage KV
Dry Withstand
50
70
95
120
175
Wet Withstand
45
60
80
100
145
Impulse Withstand Voltage kV
110
150
200
250
350
Weight kG
7
11
16
21
30
Applicabel Standard: ANSI C29.9


Relative Articles:
Pin & pin post insulators
IEC solid core post insulator main parameters and dimension
IEC standard solid core station post insulators

©2014 Zhengzhou Orient Powe Co., Ltd All rights reserved.  sales@orientinsulators.com
Orient Group is a professional manufacturer and exporter of composite suspension insulator and porcelain disc suspension insulator.